  • IEC61000-4-30 Ed.3 Class S Power Quality Analyzer
  • Monitor and record the quality of power
  • 1P2W to 3P4W
  • -20 to 50°C operating range

Product Details

HIOKI PQ3100 Power Quality Analyzer portable power meters and analyzers are best in class power measuring instruments for measuring single to three-phase lines with a high degree of precision and accuracy. The PQ3100 is a comprehensive but easy-to-use power quality analyzer for monitoring and recording power supply anomalies, allowing their causes to be quickly investigated, and also for assessing power supply problems such as voltage drops, flicker, harmonics, and other electrical issues.

Key Features
• Record data including voltage, current, power, harmonics, and flicker simultaneously along a single time axis (Flicker recording available in future firmware update)
• Measure up to 6000 A AC
• Capture all power anomalies, including instantaneous outages, voltage drops, and frequency fluctuations, while simultaneously recording trend data
• Quick Set: Easy-to-understand on-screen guide for measurement procedures
• Bundled PQ ONE application software makes it easy to create reports
• Record waveforms for up to 1 second before and 10 seconds after an anomaly occurs
• Accurately measure DC currents over extended periods of time (with an AC/DC auto-zero current sensor)
• Directly supply power to connected current sensors

Basic specifications
Measurement line type : Single-phase 2-wire, Single-phase 3-wire, Three-phase 3-wire or Three-phase 4-wire plus one extra input channel CH4 for voltage/current, (all channels AC/DC measurement)

Voltage ranges : Voltage measurement: 1000.0 V rms or DC, Transient measurement 2.200 kV peak

Current ranges : 50.000 mA AC to 5.0000 kA AC, 10.000 A DC to 2.0000 kA DC
(depends on current sensor in use)

Power ranges : 50.000 W to 6.0000 MW (determined automatically based on current range in use)

Basic accuracy : Voltage: ±0.2% of nominal voltage, Current: ±0.1 % rdg. ±0.1 % f.s. + current sensor accuracy, Active power: DC ±0.5 % rdg. ±0.5 % f.s. + current sensor accuracy, AC ±0.2 % rdg. ±0.1 % f.s. + current sensor accuracy

Measurement items :
1. Transient over voltage : 200 kHz sampling
2. Frequency cycle : Calculated as one cycle
3. Voltage (1/2) RMS, Current (1/2) RMS: one cycle calculation refreshed every half cycle
4. Voltage swell, Voltage dips, Voltage interruption, RVC(Available in future firmware update) : Voltage (1/2) RMS calculation
5. Inrush current : half-cycle calculation: Calculated as the current RMS value for current waveform data sampled every half-cycle.
6. Frequency 200 ms: Calculated as 10 or 12 cycles
7. 10-sec frequency: Calculated as the whole-cycle time during the specified 10 s period
8. Voltage waveform peak, Current waveform peak
9. Voltage, Current, Active power, Apparent power, Reactive power, Active energy, Apparent energy, Reactive energy, Energy cost, Power factor, Displacement power factor, Voltage unbalance factor, Current unbalance factor
10. Voltage crest factor, Current crest factor
11. Harmonic/ Harmonic phase angle (voltage/ current), Harmonic power: 0 th to 50 th orders
12. Harmonic voltage-current phase angle: 1 th to 50 th orders
13. Total harmonic distortion factor (voltage/ current)
14. Inter harmonic (voltage/ current): 0.5 th to 49.5 th orders
15. K Factor (multiplication factor)
16. (Available in future firmware update) IEC Flicker, ? V10 Flicker

Record : Maximum recording interval: 1 year, Maximum number of recordable events: 9999 × 365 days

Interfaces : SD/SDHC card, RS-232C (for communication/LR8410 link, available in future firmware update), LAN (HTTP server/FTP/send e-mail, available in future firmware update), USB 2.0 (for communication)

Display : 6.5-inch TFT color LCD (640 × 480 dots)

Power supply : AC adapter Z1002 (100 V to 240 V AC, 50/60 Hz, rated current 1.7 A), Battery pack Z1003 (Continuous use: 8 hr, Charging time: Max. 5 hr 30 m with AC adapter)

Dimensions and mass : 300 mm (11.81 in)W × 211 mm (8.31 in)H × 68 mm (2.68 in)D, 2.5 kg (88.2 oz) (including battery pack)

Accessories : Instruction manual ×1, Measurement guide ×1, Voltage cord L1000-05 ×1 set (Red/Yellow/Blue/Gray/Black, Alligator clip ×5, Spiral tube ×5), Color spiral tube (for identifying clamp sensor color) ×1 set, Spiral tube ×5, AC adapter Z1002 ×1, Strap ×1, USB cable (1 m 3.28 ft length) ×1, Battery pack Z1003 ×1, PQ ONE (software, CD) ×1

Product Description

HIOKI PQ3100 Power Quality Analyzer is a 3-Phase 4-Wire power quality analyzer compliant to IEC61000-4-30 class S standards and on-screen guide to deliver easy setup and testing

HIOKI 3197 Power Quality Analyzer The most comprehensive portable PQA on the market. Catch power quality problems on the fly, before they catch you Monitor for : Inrush current, Voltage ...
HIOKI 3390 Power Analyzer Measure the Secondary Side of Inverters with Cutting Edge Technology. Advanced motor analysis functions (measures the electric angle and supports vector control). ...
HIOKI 9625 Power Measurement Support Software Graphically process measurement data from Model 3169-20/21 easily on a PC Compatible devices : CLAMP ON POWER HiTESTER 3169-20, 3169-21, 316...
HIOKI 3197 Power Quality Analyzer The most comprehensive portable PQA on the market. Catch power quality problems on the fly, before they catch you Monitor for : Inrush current, Voltage ...
FLUKE 434/Log Three-Phase Power Analyzer Upgrade Kit: Adds the Logger Function of the 435 to the 434 These three-phase power quality meters help you locate, predict, prevent and troubl...